ELO (Large Drop) Sprinkler
Warehouse type sprinklers are designed for the special applications such as high level storage systems. These type of sprinklers gives the more water with more less pressure. If the users do correct pressure adjustments for ESFR Sprinklers, users don’t need any other sprinkler use for the between shelf..
Intermediate level sprinklers developed to fill protection need between shelves in storage with shelf systems. It’s essential that those sprinklers should be used with sprinkler cover ve cage to prevent water splah from above level sprinklers. If those covers aren’t used these sprinklers will not reach required temperature to activate.
ELO Upright Standard Response Sprinkler K:11.2 (160)
- Connection: ¾”npt
- Assembly: Upright
- K-Factor: 11.2 (160)
- Approvals: FM, UL, ULC
- Temperature: 68°C, 79°C, 93°C, 141°C
- Surface: Brass
- Sin: Temperature sensitive VK530 5mm Glass Bulb. – High Challenge Large Drop Sprinklers are designed to omit using sprinklers between shelves in warehouses with storage height 7.6 m and floor height is up to 9.1mm, within fires range of Group A plastics. – Distance between sprinkler’s deflector and the last pallette shouldn’t be lower than 914 mm.
Documents
ELO Upright Quick Response K:11.2 (160)
- Connection: ¾”npt
- Assembly: Upright
- K-Factor: 11.2 (160)
- Approvals: FM, UL, ULC
- Temperature: 68°C, 79°C, 93°C, 141°C
- Surface: Brass
- Sin: Temperature sensitive VK531 3mm Glass Bulb. – High Challenge Large Drop Sprinklers are designed to omit using sprinklers between shelves in warehouses with storage height 7.6 m and floor height is up to 9.1mm, within fires range of Group A plastics. – Distance between sprinkler’s deflector and the last pallette shouldn’t be lower than 914 mm.
Documents
ELO Pendent Standard Response Sprinkler K:11.2 (160)
- Connection: ¾”npt
- Assembly: Upright / Pendent
- K-Factor: 11.2 (160)
- Approval: FM, UL, ULC
- Temperature: 68°C, 79°C, 93°C, 141°C
- Surface: Brass, Chrome, White and Black
- Sin: Temperature sensitive VK536 5mm Glass Bulb. – Standart response sprinklers. – Extra wide orifice sprinklers are designed to use ın high concentration warehouses and workshops. – Lower pressure requirement means smaller pipe dimension, smaller pump capacity, that leads to a more economical solution. – Once used together with sprinkler protection cage and cover, it can be used as intermediate level sprinkler.
Documents
ELO Pendent Quick Response Sprinkler K:11.2 (160)
- Connection: ¾”npt
- Assembly: Upright
- K-Factor: 11.2 (160)
- Approval: FM, UL, ULC
- Temperature: 68°C, 79°C, 93°C, 141°C
- Surface: Brass
- Sin: Temperature sensitive VK377 3mm Glass Bulb. – Quick response sprinklers. – Extra wide orifice sprinklers are designed to use ın high concentration warehouses and workshops. – Lower pressure requirement means smaller pipe dimension, smaller pump capacity, that leads to a more economical solution. – Once used together with sprinkler protection cage and cover, it can be used as intermediate level sprinkler.
Documents
Inquiry Form
Please send us your inquiry using our contact form and we will contact you immediately.